机房建设 技术方案以及工程
技
术
参
数
介
绍
1
目 录
第一章 机房工程建设方案 ..............................................4
1 、前言 .......................................................................................................................................4
1.1 工程概况 .....................................................................................................................4
1.2 数据中心机房建设目标 ............................................................................................5
2 、土建建设方案 .......................................................................................................................6
2.1 设计依据 .....................................................................................................................6
2.2 设计要求 .....................................................................................................................7
2.3 地面装修说明 .............................................................................................................7
2.4 吊顶装修说明 .............................................................................................................7
2.5 隔断墙体装修说明 ....................................................................................................7
2.6 墙体装修说明 .............................................................................................................8
2.7 门窗装修说明 .............................................................................................................8
3 、空调通风系统设计 ...............................................................................................................9
3.1 设计依据 .....................................................................................................................9
3.2 空调改造方案 .............................................................................................................9
3.3 空调技术要求 .............................................................................................................9
3.3 室内空调参数 ...........................................................................................................11
3.4 机房新风系统 ...........................................................................................................11
4 、电气设计说明 .....................................................................................................................12
4.1 设计依据 ....................................................................................................................12
4.2 供电电源 ....................................................................................................................13
4.3 不间断电源系统设计 ................................................................................................13
4.4 配电设计 ....................................................................................................................16
4.5 照明设计说明 ............................................................................................................17
2
5 、机房安全系统设计 .............................................................................................................17
5.1 设计依据 ...................................................................................................................18
5.2 防雷接地设计说明 .....................................................................................................18
5.3、消防报警及灭火系统 ............................................................................................20
5.4 机房 保安监控系统 ....................................................................................................21
5.5 机房门禁系统 ...........................................................................................................21
6 、机房设备总控系统设计概述 ............................................................................................21
7 、机综合布线系统设计概述房 ............................................................................................24
7.1 设计依据 ....................................................................................................................24
7.2 机房综合布线 ............................................................................................................25
7.3 KVM 网络管理 ............................................................................................................25
7.4 机柜 ............................................................................................................................26
第一章 机房工程建设方案
1、前言
数据中心基础设施的建设,很重要的一个环节就是计算机机房
的建设。计算机机房工程不仅集建筑、电气、安装、网络等多个专
业技术于一体,更需要丰富的工程实施和管理经验。计算机房设计
与施工的优劣直接关系到机房内计算机系统是否能稳定可靠地运行,
是否能保证各类信息通讯畅通无阻。
计算机机房既要保障机房设备安全可靠的正常运行,延长计算机系
统使用寿命,又能为系统管理员创造一个舒适的工作环境,能够满
3
足系统管理人员对温度、湿度、洁净度、电磁场强度、噪音干扰、
安全保安、防漏、电源质量、振动、防雷和接地等的要求。所以,
一个合格的现代化计算机机房,应该是一个安全可靠、舒适实用、
节能高效和具有可扩充性的机房。
1.1 工程概况
xxx 机房面积大约为 50m2 左右 , 拟改造成国家标准机房,作为
大楼的数据中心。
中心机房按功能划分配电区、气体灭火区、网络机房、主控间、
办公间。
1.2 数据中心机房建设目标
我公司将多年的机房建设经验及对 xxx 总部机房需求的深刻理
解,将设计目标分析如下:
机房建设将以国家 A 类标准进行建设
机房土建装修设计(将满足机房防尘、防潮、抗静电、电磁屏
4
蔽等机房环境需求)
机房供配电系统设计(将满足机房高质量、持续、稳定供电需
求)
机房精密空调系统设计(将满足机房温度调节、湿度调界、风
量调节等需求)
机房安全系统(将满足机房防盗、门禁、防雷接地、消防灭火
等物理安全需求)
机房环境监控系统(将满足机房设备运行情况监控)
机房 KVM 管理(将满足机房内服务器、网络设备管理需求)
5
广州莱安智能化系统开发有限公司成立于是 2002 年,专业从事数字
网络视频监控系统、智能视频分析、机房动力环境监控、机房建设、
雷达测速、闯红灯电子警察抓拍、电子治安卡口、智能控制等智能
化系统开发的大型综合型企业,欢迎来电洽谈业务!
6
2 、土建建设方案
2.1 设计依据
《电子计算机场地通用规范》( GB/T-2887-2000 )
《电子计算机机房设计规范》( GB50174-93 )
《计算站场地安全要求》( GB 9391-88 )
《防静电活动地板通用规范》( GB 6650-86 )
《高层民用建筑设计防火规范》( GB 50045-95 ) 2001 年版
《建筑内部装修设计防火规范》( GB 50222-95 )
《电磁辐射防护规定》( GB8702-88 )
《电子计算机机房施工及验收规范》( SJ/T 30003-97 )
《建筑装饰工程施工及验收规范》( JGJ 73-91 )
《民用建筑工程室内环境污染控制规范》( GB50325-2001 )
《办公建筑设计规范》( JGJ67-89 )
2.2 设计要求
装修需要满足防火、放静电、防尘、防盗、防噪音、屏蔽需求 .
7
2.3 地面装修说明
数据中心机房地板铺设高度为 0.35 米,为空调下送风和强弱电
管道预留空间,机房地板采用华东环球优质 600X600 全钢 耐磨 抗
静电地板, 在支架 下 边刷粘 和 漆 , 在 地板下 边在 UPS 区 域加固 , 并
做散立支撑 ,分 载UPS承 重 问题 ,办公区采用高 档木 地板。地板
下 刷 防尘 漆 。
2.4 吊顶装修说明
数据中心机房所有 天花 全部采用 铁立达微孔铝 合 金金属 板 吊顶 ,
顶 内 回 风配 套 主 龙骨 , 次龙骨 , 龙骨 采用 40X4 角 钢 支撑 。 梁 、 顶
做 防尘 处 理。
2.5 隔断墙体装修说明
网络机房和主控室 之 区 域 间的 隔墙 采用 12mm 双 层防火 玻璃隔断 ,
中间安装防火 隔 音 棉 , 并 进行防火 处 理, 耐 火 极限 不 低 于 0.5h ,
8
满足防火规范要求。
2.6 墙体装修说明
机房配电区设 置 防火区,基层面板安装 四川吉祥铝塑 板,内 填 充
防火 棉 ,机房 其他 区 域 设 置双 层 白色铝塑 板饰面, 并根 据现场装修
尺寸做 分 缝 安装, 并 按 照 接地要求对 铝塑 板 做 接地 处 理。按 照 机房
环境要求,机房内 墙 面进行 隔 音、防火、屏蔽 处 理, 墙 面 刷 高 档乳
胶漆 。
2.7 门窗装修说明
机房 出口 设 置向疏散方向开启且 能 自 动关 闭 的门。机房主 入口 、
主控间和网络机房 之 间安装门禁系统,房间 里 设 置出 门按 扭 , 外边
刷卡 ,保证 在 火 灾发生时 ,门禁系统 自 动 打开 ,机房 里 面的人员可
自由出去 , 在 火 警 情况下可保证人员安全 撤离 。
在 主机房和 辅助 机房的 窗户都换 作成 铝 合 金推拉窗户 , 原 有 玻
9
璃窗户 全部 取 消。 防护区 隔墙 和门 窗耐 火 极限 要求不 低 于 0.5h 。
在 主控室进门 口 安装防火防盗门, 在玻璃隔墙处 安装 玻璃自 动
门, 并 保证门 筐厚 度 符 合门禁的安装需要, 窗帘颜色选 用要和机房
颜色 配 套 。
3 、空调通风系统设计
3.1 设计依据
1 、《电子计算机房设计规范》
2 、《高层民用建筑与空气调节设计规范》
3 、《采 暖 通风与空气调节设计规范》
4 、《通风与空调工程施工质量验收规范》
5 、气 象资料 有关数据 ;
6 、国家有关设计规范:
3.2 空调改造方案
1 )数据中心机房面积约 45m2 ,配 置 1 台 机房专用空调, 单
10